You can make a contribution to support
Simple
trACtors online, safely and
securely, using our PayPal account.
3 Pole Regulators and How Regulators Operate
In this article, if you have any questions regarding the meaning of the
terminology of items in the section please refer to previous sections as they
provide the background for this one.
This article will deal specifically with 3 pole regulators. This is the regulator that is
used on the long frame generators, usually on the horizontal shaft engines.
There are three units that control the charging. On the left are the Cut-out
contacts. They connect and disconnect the armature from the battery. When the
generator output voltage reaches 11.8 or more, the contacts are pulled
together. When they pull together, the armature A terminal is connected through the
heavy wires [bold black] through the heavy black wires on the current limit
[center] section. Note the cutout section has a fine winding also. This winding
is connected to ground [also called shunt connected] and provides the magnetic
energy to pull the contacts together. In the real regulator, the contacts have a
specific air gap and there is a spring pulling the contacts open. The spring
tension is adjusted to allow the contacts to come together from 11.8 to 13
volts. The heavy winding around the outside provides additional pull on the
contacts when current is flowing to the battery to prevent arcing when the
voltage out of the armature is very close to pull in voltage. At the point when
the voltage at the armature is less than the battery voltage current starts to
flow from the battery to the armature. This reverse flow of current reverses the
polarity of the magnetic field produced by the heavy current winding. This
magnetic field opposes the field created by the small wire shunt winding. This
cancellation of magnetic fields provides a clean release of the contacts.
Remember that on these starter generators the output is controlled by
grounding the field terminal and are known as an [A] circuit type. Higher output
automotive generators may need voltage applied to the field to energize the
field. These are known as [B] circuit generators. The voltage regulators are
built different. Instead of controlling the ground they have the control
contacts arranged to put voltage on the field terminals. If you are using this
information to work on a farm tractor or automotive application be sure to
determine the type of generator you have, as they are NOT interchangeable
The center pole is the current regulator. This section regulates the maximum
current the generator is allowed to put out so it does not destroy itself.
It
has a pair of contacts that are normally closed [NC]. When the generator voltage
starts to flow through the cut-out section all of the current flows through the
heavy winding in this coil. Since this is a series winding, the more current the
stronger the magnetic field and the greater pull on the contact arm. When the
current exceeds a predetermined level, [10 amps normally on the long frame
starter generators] the spring tension on the contacts allows the contacts to
break. Note that the current section contacts are in series with the voltage
section contacts and the two provide the ground path for the field winding of
the generator. When this contact opens it removes the hard ground on the
generator field [F] terminal. Note: There is a resistor connected to the [F] and
ground. This provides a reduced current ground path for the field winding in the
generator. This reduces the output of the generator. When the generator output
drops the spring pulls the current contacts back together and bypasses the
resistor to ground. The generator is again running full output. If the current
exceeds the set level the contacts again break and the cycle repeats. If the
load is too high the contacts will be continuously vibrating to limit the
current to the preset level. This allows the charging current to be limited to
the maximum safe output of the generator preventing damage to the unit.
On the right is the third unit. The voltage control section. It consists of a
pair of normally closed [NC] contacts connected in series with the current
control contacts to ground and to the field [F] terminal. Under these contacts
is a coil wound of very fine wire wound around a metal pole piece, as the coils
on the other two units are. The air gap and the spring tension on these
terminals are adjusted to control the voltage coming from the armature. This is
normally set from 14 to 14.5 volts. Since this coil is connected [parallel]
across the armature terminal to ground its magnetic field is created relative to
the voltage applied to it. When the voltage reaches the preset level the
contacts break opening the direct ground path through the current contacts and
leaving the resistor across the [F] terminal to ground. The generator armature
output drops the contacts snap shut and the generator is full output [also
called full fielded] again. It works exactly like the current section only it
responds only to voltage output. There is commonly one more resistor that goes
from the [F] terminal the armature contact of the cut-out. I didn’t include it
because its purpose is to provide a damping effect when the control contacts
open and reduce the arcing of the contacts. It plays no part in the
"controlling" operation of the regulator. When the unit is running the
contacts are constantly vibrating. They seldom open more than a couple of
thousandths of an inch. The contacts are made of Tungsten and are designed to do
this for years. Actually when you look at how long they last, it is almost
unbelievable.
This is a picture of a 3 unit or 3 pole regulator. Note
that the
Voltage control coil is wound of many turns of very fine wire. The Current unit
is wound with few turns of VERY large wire and the cut-out unit is wound like
the voltage coil on the inside and has a very heavy series winding wound over
the inner shunt winding. The heavy wires are in series and ALL of the charging
current flows through them. They create their magnetic flux from all of the
current they carry and the flux is relative to the amount of current. The fine
wires are shunt wound, meaning that they are across the voltage source to ground
and the magnetic flux they create is proportional to the voltage across the
coil. All are wound around an iron rod or pole piece. In all three, the contacts
are operated by the magnetic flux pulling on the arm that the contacts are mounted
on, causing the contacts to make contact or break contact. The contacts are held in their
static positions by a spring on the rear of the contact arm. Note the little tab
at the back of the arms. Below it is a tab that adjusts the spring tension for
calibration.